Stabilizers helps you to keep the o/p voltage with a tolerance of 1% & works with efficiency more than 98%.
Specifications | 1 Phase | 3 Phase Unbalanced Air Cooled |
3 Phase Unbalanced Oil cooled |
---|---|---|---|
Ratings KVA | 2-20 | 3-150 | 2-2000 |
Type of cooling | Air | Air | Oil |
Input Voltage Range (VL-L) | 130-280,170-270V | 310-480 / 340-480 / 360-460 | |
Output Voltage(VI-L) | 220 V | 415 (380V / 400V-Optional) | |
Output Voltage Regulation | 1% of nominal voltage | ||
Input Frequency Range | 47Hz-53Hz | ||
Efficiency | >97% | ||
Effect of Load Power Factor | Nill | ||
Waveform Distortion | Nill | ||
Types of Servo Control | Micro Controller based TrueRMS sensing and correction | ||
Servo Motor Drive | Triac based drive for AC Step Synchronous motor | ||
Under / Over Voltage cutof | Electronic cutoff circuit with graded time delay, set @ +5% / -10% of nominal output voltage | ||
Overload Cutoff | CT based Electronic cutoff circuit with graded time set @ 110% of rated full load current | ||
Short Circuit Protection | MCB / MCCB provided up to 100KVA, Above 100KVA HRC fuse (MCCB OPTIONAL) | ||
Single Phasing Prevention | Provided | ||
Phase Reversal Trip | Provided | ||
Stabilizer bypass | Provided up to 50 KVA 3-phase: Optional > 50 KVA | ||
Transient Suppression | Sprike Suppression through MOV is provided (Surge Arrestor is optional) | ||
Emergency Off Switch | Provided | ||
Frequency Cut-Off Protection | Optional | ||
Input High Voltage Trip | Optional | ||
Resetting Mode | Manual / Auto option provided with programmable time delay | ||
Display Type | LED Display | ||
Parameter Display | Input & Output Voltages (Line & Phase), Output Currents & Frequency,Fault Annunciation | ||
LED Indications | Non Latching LED Lamps for Output ON, MCB Trip, Stabiliser Bypass (If Bypass Switch is provided) | ||
Input / Output Terminations | Din Connectors up to 100 KVA, Busbar / Bolted terminals for ratings >100 KVA |
*Due to continous improvements actual specifications may change without prior notice