Power On Line UPS

- Double conversion Online UPS
- Input power factor near unity
- Low Input current distortion
- Active power factor correction
- High efficiency
- Inbuilt galvanic isolation transformer
- Advanced network connectivity
- IGBT based design

Optional

  • Redundant UPS for 24X7 operation (hot standby and load sharing)
  • Harmonic filter at the UPS input (Active / Passive)
  • Mobile Connectivity
  • RS 232 / Remote Monitoring

Technical Specifications: SMART (ONLINE UPS 1ph-1ph)

Capacity 10KVA 15KVA 20KVA 25KVA 30KVA 40KVA
Technology DSP with IGBT
DC Bus 360V
Input
Input Voltage 415 V 3Ph and N
Input Power Factor @ 100% Load 0.99
Input current harmonic distortion (THD) < 10%
Input Voltage Window 330 - 470V
Input Frequency 45-55Hz
Input PFC > 0.95
Power Soft start for 0 20 seconds power
Rectifier IGBT based Full bridge
Voltage Regulation (+)1%
Ripple Voltage < 2%
Converter Protection Advanced Electronic Protection for device safety backed up with MCB’s/ MCCBs & fast acting fuses
Inverter
Inverter Type IGBT based MPWM with instantaneous Sinewave Control
Power Factor 0.8 lag
Nominal Voltage 220VAC / 230VAC
Regulation ( ± ) 1%
Frequency 50Hz ± 1Hz
Total Harmonic Distortion <2% for linear load, <6% for non linear load
Over Load Capacity 100%-Continuous : 125% -1 Minute : 150% 5 Seconds
Transient Response Remains within +/- 5% & recover to normal within 20 msec
Nominal output current 34A 48A 64A 80A 98A 128A
Crest Factor 3:1
Waveform True Sinewave
Inverter Protection Advanced Electronic Protection for device safety backed up with MCB’s/ MCCBs & fast acting fuses,high speed pulse by pulse electronic device protection over voltage / under voltage protection, Electronic over current trip
Bypass
Manual Bypass Provided
Static bypass(Optional) Optional Feature
Efficiency
Efficiency - 100% load >86% to > 88 %
Battery
Battery Type SMF/ TUBULAR
No. of Batteries 30
Voltage 360V
Battery Low advance warning at 11 v / battery
Battery Low cut off at 10.5 V / Battery
Charger CCVA
Alarms Input / Low / Fail | Output Overload | Over Temperature | Battery low
Display
LCD Display Input Voltage | Output Voltage | Load current | Output Overload | Output Frequency
LED INDICATIONS
(Single LED with multi function)
Mains on | UPS on | Battery Low | Overload
Protection
Protecting the load
Output Under Voltage
Output Over Voltage
Protects the load and its components from premature failure
Output Single Phase prevention Protects the connected three phase loads & its components from premature failure
Output short circuit with pulse Protects against false tripping & complete shutdown in case of surge
by pulse current limit up to 200μsecs.Protects 300% for 15 msecs,500% for 5msec &1000% for 1.5 msec of the rated current Power drawn by the load (non linear loads)
Neutral drift Neutral failure
Lightning
EMI & Harmonics in the input
Neutral
High voltage transient protection & Electrostatic discharge protection as per IEC 62040-2
Galvanic isolation provides complete isolation between output neutral and Input & the the output is fully protected against neutral drifts,voltage avalanches like lighting & input harmonics commonly found in the input side.
Protecting the UPS
Input MCCB / MCB Protects th input from very large current caused by short circuit or due to a damaged internal component and avoids further damage to the equipment
Input Under Voltage / Over Voltage Prevents damage of components in the input sensing & the converter devices
Over Temperature Protection Protects the Inverter & Converter magnetics and switching devices against premature failure
Over Load protection Protects the Inverter components against premature failure
Input Under Voltage / Over Voltage
'High voltage transient protection & Electrostatic discharge protection as per IEC 62040-2
Protects the Inverter & Converter magnetics and switching devices against premature failure
External Magnetic field Protection Protects against external power frequency magnetic field
Environmental
Acoustic Noise level <60db @ 1.5 meter
Ambient Temperature 0 to 40 Deg C
Storage Temperature -10 to 70 Deg C
Humidity Up to 95% RH Non condensing
Altitude < 3000 Feet above sea level (without derating)
Extreme climatic conditions AC Environment is required if the temperature goes beyond the normal operating temperature (0-40 deg C)
Physical
Enclosure Protection Grade IP - 20
Cooling Forced Air
Cable Entry Front side bottom
Testing Standard As per IEC 62040 - 3

*Due to continous improvements actual specifications may change without prior notice